Q370 - FAQ: Modelling a Concrete Floor

Question


I am modeling a substation grounding system using MALT where there is a control building which has a concrete floor. After running MALT, it shows the maximum acceptable touch potential is exceeded inside the building. Can we assume the concrete floor is an isolated layer? Should we be concerned about the touch voltage problem for this area even though it has a concrete floor? Why?

Answer


It is usually not a good assumption to consider concrete as an isolating material. Unless it is treated with special chemicals, concrete will absorb water from its surroundings and become substantially conductive. However, if there is rebar embedded in the concrete, then the entire concrete area can be considered an equipotential. If the rebar is connected to the grounding grid, then the concrete area can be ignored for the purpose of safety calculations.

Therefore, it is quite important to determine if there is rebar in the concrete and, if so, if it is connected to the grounding grid. If not, the safest thing to assume is to ignore the presence of the concrete altogether.
Related Articles
No Related Articles Available.

Article Attachments
No Attachments Available.

Related External Links
No Related Links Available.
Help us improve this article...
What did you think of this article?

poor 
1
2
3
4
5
6
7
8
9
10

 excellent
Tell us why you rated the content this way. (optional)
 
Approved Comments...
No user comments available for this article.
Created on 8/7/2002.
Last Modified on 9/9/2016.
Last Modified by Administrator.
Article has been viewed 7229 times.
Rated 5 out of 10 based on 1221 votes.
Print Article
Email Article

Module Border Module Border
©Safe Engineering Services & technologies ltd. All Rights Reserved.